Fixed: Short disruption cooling for BIT-2BCD

Fixed: Short disruption cooling for BIT-2BCD

18-05-2018 16:44:11 - 18-05-2018 17:30:00
Status: opgelost

Around 16:27 there was a short disruption of the cooling for BIT-2BCD. This short disruption was triggered by a powerdip from the power grid.

The powerdip triggered phase monitoring of the chillers for BIT-2BCD, which causes that the chillers where shut down. As a result the temperature in some places in BIT-2B and BIT-2C has been higher than normally on those places.

Follow the incident on our website for updates concerning this incident.


Update placed at 18/05/2018, 16:50
Colleagues have manually switched on the chillers around 16:28.

BIT is researching how we can prevent an incident like this.


Update placed at 18/05/2018, 17:05
The incident has been resolved. If you have any questions regarding this incident, please contact the Customer Care department by phone on +31 (0)318 648 688 or by email on support@bit.nl.